| Nominal Conductor Area
sq. mm |
Number And Size
of Wire
No/mm |
Radial Thickness of Insulation
mm |
Radial Thickness of Sheath
mm |
Nominal Overall Dimensions
mm |
E.C.C.
Number And Size of Wires
mm |
Approx Weight
kg/km |
Maximum Resistance Per 1000
metres of cable at 20ºC
ohm |
| 1.0 | 1/1.13 | 0.6 | 0.9 | 7.8 x 4.4 | 1/1.13 | 72 | 18.1 |
| 1.5 | 1/1.38 | 0.7 | 0.9 | 8.3 x 4.6 | 1/1.13 | 79 | 12.1 |
| 2.5 | 7/0.67 | 0.7 | 1.0 | 10.6 x 5.4 | 7/0.67 | 135 | 7.41 |
| 4.0 | 7/0.85 | 0.8 | 1.0 | 12.6 x 6.5 | 7/0.67 | 183 | 4.61 |
| 6.0 | 7/1.04 | 0.8 | 1.1 | 14.0 x 7.3 | 7/0.67 | 252 | 3.08 |
| 10.0 | 7/1.35 | 1.0 | 1.2 | 17.4 x 8.8 | 7/0.85 | 387 | 1.83 |
| 16.0 | 7/1.70 | 1.0 | 1.3 | 20.3 x 10.1 | 7/1.04 | 551 | 1.15 |
PVC Insulated PVC Sheathed Flat Two Core with Earth
PVC Insulated PVC Sheathed
Flat Two Core With Earth Continuity Conductor 300 / 500 Volt To KS 04-453
Category: 3 PVC Insulated Sheathed, PVC Insulated Wiring Cables, Two Core
PVC Insulated PVC Sheathed Flat Two Core with Earth
Related products
-
PVC Insulated PVC Sheathed Flat Two Core
PVC Insulated PVC Sheathed Flat Two Core 300 / 500 Volt Grade To KS 04-453 -
Single Core PVC Insulated Unsheathed
Single Core PVC Insulated Unsheathed 450/750 Volts Grade To KS 04-453 -
PVC Insulated PVC Sheathed Single Core
PVC Insulated PVC Sheathed Single Core 600/1000 Volt Grade To KS04-194 & BS 6346